Product Introduction:
ACCU-100 Microgrid Coordination Controller is an intelligent coordination controller used in microgrid,distributed generation,energy storage and other fields.The device meets the requirements of the system to meet the access of photovoltaic systems,wind power generation,energy storage systems,charging piles and other equipment.Through all-weather data collection and analysis of the microgrid system,the operation status of photovoltaic,wind energy, energy storage system and charging piles is monitored.The health status of the microgrid is analyzed,and on this basis,the optimal control strategy is obtained with the goal of safe and economical optimal operation,and then the microgrid is implementedRegulation and control to achieve real-time dynamic regulation of microgrid distributed energy,energy storage system,and load,and promote local use of new energy.Improve grid operation stability and compensate for load fluctuations;effectively manage microgrid demand and improve microgrid operation.Improve operation efficiency,reduce power supply costs,and ensure safe,reliable and economical operation of microgrids.
Keywords:
Coordination controller,energy storage, PV , wind power,power generation,EV charger
Product Parameters:
ACCU-100 microgrid controller is mainly responsible for data collection and local control strategy of industrial and commercial photovoltaic storage and charging new energy power stations.And the interaction of cloud data.Supported capacity: energy storage capacity:≤400kW,photovoltaic capacity:≤400kWp

project |
Specification |
processor |
ARM Cortex-A7 528MHz |
Memory |
256MB DDR3 + 256MB NAND Flash |
Frequency and power consumption | 50Hz (45〜65Hz), power consumption ≤10W |
Supply voltage |
AC/DC 220V (85-265V) |
RS485 Serial Port |
8-way optocoupler isolation |
RJ45Network port |
2-way 10/100M adaptive |
Other interfaces |
1*RS232 management serial port + 1*USB2.0 + SD Card standard slot + 4G interface; (DI, DO optional) |
Protocol support |
Device side: Modbus Rtu/TCP, DL/T 645-1997, DL/T 645, etc.; |
Master side: Modbus TCP, 104, SNMP, MQTT protocol, etc.; | |
Security |
Power frequency withstand voltage: 1 minute between power supply and communication terminals: 2kV (220V equipment), 1.5kV (24V equipment) |
Insulation resistance: Under normal test atmospheric conditions, the input and output terminals to the housing> 100MΩ | |
Working temperature: -20℃〜+55℃ | |
environment | Storage and transportation temperature: -25℃〜+70℃ |
Relative humidity: ≤95% (+25℃) | |
Altitude: ≤2500m | |
GB/T 17626.2-2018 Electrostatic discharge immunity test Level 4 | |
Electrical properties |
GB/T 17626.3-2016 Radio frequency electromagnetic field radiation immunity test Level 3 |
GB/T 17626.4-2018 Electrical fast transient burst immunity test Level 4 | |
GB/T 17626.5-2019 Surge (impact) immunity test Level 4 |
System Architecture

Post time: Feb-11-2025