BM200 Series explosion-proof isolation barrier

Short Description:

 Input type: Current/Voltage/Thermal resistance Pt100/Resistance/Thermocouple

 Transmission accuracy: 0.2%

● Input:  0~20mA /4~20mA ,0~5V /0~10V /1~5V  (Distribution voltage: 12V/20mA) PT100 /0~10K

● Output: 0~20mA /4~20mA , 0~5V /1~5V , 0~10V 

 Power Supply: 20~35V DC 

● Response Time: 5ms to reach 90% of final value

● Installation: DIN Rail

● Standard&Certificate: CE


Product Detail

Download

Certification

BM200-□□/□-B11 outline dimension

1
2

BM200-□□/□-C□2 outline dimension

3
4

Type of products

111

Technical parameter

 Channel type Single-way input and single-way output, single-way input and double-way output,double-way input and double-way output
Input type Current/Voltage/Thermal resistance Pt100/Resistance/Thermocouple
 Input signal 0~20mA /4~20mA0~5V /0~10V /1~5V (Distribution voltage: 12V/20mA) PT100 /0~10K
 Output signal 0~20mA /4~20mA (Safe side input); Load resistance: ≤550Ω 0~5V /1~5V (Safe side input); Load resistance: ≥330K0~10V (Safe side input); Load resistance: ≥500K
Transmission accuracy 0.2%
Temperature modulus 50ppm/℃ (The output signal is current)
Response time 5ms to reach 90% of final value(RTD Pt100/resistance/thermocouple input: 1s to reach 90% of final value)
Power supply 20~35V DC
Work temperature -20℃~+60℃
Fix mode Rail installation
 Dielectric strength Intrinsically Safe and Non-Intrinsically Safe ≥2500V AC; Power supply and Non-Intrinsically Safe ≥500V ACNote:Intrinsically Safe is input, Non-Intrinsically is output

Outline dimension

Product category Type of products Outline dimension
 

 

BM200

BM200-□□/□-B11(single-way input and single-way

output)

99mm*114.5mm*12.5mm
BM200-□□/□-C□2 (single-way input and double-way

output/double-way input and single-way output)

99mm*114.5mm*22.5mm

  • Previous:
  • Next:

  • Related PRODUCTS