ASJ series residual current operated relay can be combined with low voltage circuit breaker or low voltage contactor to form a residual current protection device, which is mainly used for the TT and TN system distribution lines with AC 50Hz and rated voltage of 400V and below. It is used to protect the electrical circuit form ground faults, prevent equipment damage caused by earth fault current and electrical fire accidents, and can also be used to provide indirect contact protection against personal electric shock hazard.
Display
LCD display
Comunication
RS485 Modbus-RTU
Frequency
50Hz±5Hz
Auxiliary power supply
AC110V, AC220V, DC85 ~270V
(permissible error ±10%)
Consumption
≤5W
Installation
DIN rail 35mm
Dimension(L*W*H)
85×54×64mm
Technical Parameter |
Indicator |
||
AC type |
A type |
||
Power supply |
Voltage range |
AC110V、AC220V (±10%) |
AC/DC85~265V |
Power dissipation |
≤5W |
||
Input |
Rated residual operating current I△n |
0.03、0.1、0.3、0.5(A) |
0.03、0.05、0.1、0.3、0.5、1、3、5、10、30(A)note 3 |
Limit non-driving time △t |
0.1、0.5(s) |
0、0.06、0.1、0.2、0.3、0.5、0.8、1、4、10(s)note 4 |
|
Rated residual non-operating current I△no |
50%I△n |
50%I△n |
|
Performance characteristics |
Sinusoidal AC |
Sinusoidal AC and pulsating DC |
|
Frequency |
50Hz±5Hz |
50Hz±5Hz |
|
Operating range |
-20% ~ -10%I△n |
-20% ~ -10%I△n |
|
Output |
Output mode |
One is normally open and another is for transformation |
One is normally closed or open, and another is for transformation |
Contact capacity |
5A 250VAC 5A 30VDC |
AL1:8A 250VAC; 5A 30VDC AL2:6A 250VAC; 5A 30VDC |
|
Reset mode |
Local reset or remote reset |
Local reset, remote reset or automatic reset |
|
Installation and use environment |
Temperature |
Run temperature:-20℃ ~ +55℃,Storage temperature:-30℃ ~ +70℃ |
|
Humidity |
≤95%RH,no condensation, and no corrosive gas places |
||
Elevation |
≤2000m |
||
Class of pollution |
Grade three |
||
Installation category |
Type Ⅲ |
Note 3: ASJ10L-LD1A rated residual operating current IΔn is 10mA~30A continuously adjustable;