ASJ10L-LD1A Digital Earth Leakage Relay

Short Description:

● A-type residual current measurement

● Rated residual operating current can be measured

● Limit non-driving time can be set

● Two sets of relay output (settable)

● Transformer breakage alarm can be set

● Pre-alarm value can be set

● Return value can be set

● With on-site display, remote “test”, “reset”

● LCD display, 25 event records


Product Detail

Parameter

General

ASJ series residual current operated relay can be combined with low voltage circuit breaker or low voltage contactor to form a residual current protection device, which is mainly used for the TT and TN system distribution lines with AC 50Hz and rated voltage of 400V and below. It is used to protect the electrical circuit form ground faults, prevent equipment damage caused by earth fault current and electrical fire accidents, and can also be used to provide indirect contact protection against personal electric shock hazard. 

Display
LCD display

Comunication
RS485 Modbus-RTU

Frequency 
50Hz±5Hz

Auxiliary power supply
AC110V, AC220V, DC85 ~270V
(permissible error ±10%)

Consumption
≤5W

1

Installation

DIN rail 35mm

Dimension(L*W*H)

85×54×64mm

2

Typical connection

3
4

Site installation pictures

6

  • Previous:
  • Next:

  • Technical parameters

    Technical Parameter

    Indicator

    AC type

    A type

    Power supply

    Voltage range

    AC110VAC220V

    ±10%

    AC/DC85~265V

    Power dissipation

    ≤5W

    Input

    Rated residual operating current In

    0.030.10.30.5(A)

    0.030.050.10.30.51351030(A)note 3

    Limit non-driving time △t

    0.10.5(s)

    00.060.10.20.30.50.81410(s)note 4

    Rated residual non-operating current Ino

    50%In

    50%In

    Performance characteristics

    Sinusoidal AC

    Sinusoidal AC and pulsating DC

    Frequency

    50Hz±5Hz

    50Hz±5Hz

    Operating range

    -20% ~ -10%In

    -20% ~ -10%In

    Output

    Output mode

    One is normally open and another is for transformation

    One is normally closed or open, and another is for transformation

    Contact capacity

    5A 250VAC

    5A 30VDC

    AL1:8A 250VAC; 5A 30VDC

    AL2:6A 250VAC; 5A 30VDC

    Reset mode

    Local reset or remote reset 

    Local reset, remote reset or automatic reset

    Installation and use environment

    Temperature

    Run temperature-20℃ ~ +55℃Storage temperature-30℃ ~ +70℃

    Humidity

    ≤95%RHno condensation, and no corrosive gas places

    Elevation

    ≤2000m

    Class of pollution

    Grade three

    Installation category

    Type Ⅲ

     

    Note 3: ASJ10L-LD1A rated residual operating current IΔn is 10mA~30A continuously adjustable;

    Note 4: ASJ10L-LD1A limit non-driving time Δt is 0~10S continuously adjustable.