APM830 AC Multi-function Energy Meter

Short Description:

● Measurement: U,I,P,Q,S,PF,F

● Current Rating: AC 1A,5A

● Voltage Rating: 100V, 110V, 400V, 690V AC

 Frequency: 45~65Hz

● Accuracy: 0.2S

● Communication (Main Body): RS485 (MODBUS-RTU)

● Communication (Expanded): PROFIBUS-DP; Ethernet; Secondary RS485

● Extra Function: 8DI/2DO; 8AI/4AO; Multi-rate

● Display: Dot matrix LCD

● Dimension: 96*96*90mm (L*W*H)

● Harmonic: Total harmonics ,odd and even harmonics

● Installation: Panel Embedded (Cut-out –92*92mm)

● Power Supply: 85~265V AC/DC; 115~415V AC/DC

● Standard&Certificate: CE


Product Detail

Parameters

General

APM series power meters of ACREL are power meters that are designed according to IEC standards and synchronized with international advanced technology.

APM series meters have full power measurement, energy statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of the quality of power supply network.

Technical Parameter

1

Dimension

2

Production Selection

3

Wiring

4

Low-voltage 3-phase 4-wire

5

High-voltage 3-phase 3-wire (2PT&2CT)

Installation

6

  • Previous:
  • Next:

  • Technical Parameters

    display Display method Dot matrix LCD
    Resolution 192 * 160
    Backlight White LED
    Visible area 69mm*62mm(2.8Inch / 6.66inch)
    Signal Electrical network Three-phase three-wire, three-phase four-wire, see the wiring diagram;
    Frequency 4565Hz
    Voltage Rated valueAC 3*57.7/100VAC 3*63.5/110VAC 3*230/400VAC 3*400/690V690V direct connection on voltage input terminalL-L
    Overload: 1.2 times rated value(continuous); 2 times rated value /1 second;
    Power consumption: < 0.5VA (per channel);
    Current Rated valueAC 3x 1 (1.2) AAC 3×5(6)A support 4 mm2 line access;
    Overload: 1.2 times rated value(continuous); 10 times rated value/1 second;
    Power consumption: < 0.5VA (per channel);
    Measurement accuracy Voltagecurrent IEC 61557-12 class 0.2
    Voltage imbalance IEC 61557-12 class 0.2
    Voltage harmonics, current harmonics IEC 61557-12 class 2  Note1
    frequency IEC 61557-12 class 0.2s
    Active power IEC 61557-12 class 0.2s
    Reactive power IEC 61557-12 class 1s
    inspecting power IEC 61557-12 class 0.2
    Active energy IEC 62053-22 – Active energy0.2S
    Reactive energy IEC 62053-24 – Reactive energy0.5S
    Power Quality Recording wave 20 waveforms, 10 waves before and after;
    Waveform capture Each waveform is stored at 128 cycle points; the TF card is supported to expand the recorded data, and the customer needs to manually pull the line chart through Excel.
    Switch inputs Dry contact inputs, built-in power supply;

    Response time: less than 300ms

    Relay outputs Contact type: open contact in main part, changeover contact in module;

    Contact capacityAC 250V/3A  DC 30V/3A

    Pulse output of energy Output mode: Optocoupler pulse with open collector;

    Pulse constant10000imp/kWh(default),For details, see 6.2 Input Settings.;

    Analog outputs DC 020mA420mA05V15V Output, accuracy grade 0.5%, load resistance ≤500Ω at current output, load resistance ≥2KΩ at voltage output; overload: 1.2 times rated value (continuous);
    Analog inputs DC 020mA, 420mA, 05V, 15V input, accuracy grade 0.5; overload: 1.2 times rated value (continuous);
    TF Storage card Standard TF card with 8G capacity, maximum support for TF card with 32G capacity;
    communication RS485 interface/Modbus-RTU protocol and DLT645 protocol

    Profibus-DP interface/Profibus-DP protocol;

    RJ45 interface (Ethernet) / Modbus-TCP, http, DHCP and other protocols;

    Power supply Working range: AC/DC 85V265V or AC/DC 115415V(P2);

    Power consumption: Power consumption of the main part ≤ 15VA;

    Safety Power frequency withstand voltage The power frequency withstand voltage between the shell and the auxiliary power supply, each input and output terminal group is AC 4kV/1min;

    The power frequency withstand voltage between the auxiliary power supply and each input and each output terminal group is AC 2kV/1min;

    The power frequency withstand voltage between the voltage input and other input/output terminal groups is AC 2kV/1min;

    The power frequency withstand voltage between the current input and other input/output terminal groups is AC 2kV/1min;

    The power frequency withstand voltage between the relay output and other input/output terminal groups is AC 2kV/1min;

    The power frequency withstand voltage between each terminal group of switch input, communication, analog output and pulse output is AC 1kV/1min;

    Insulation resistance Inputsoutputs to the shell>100MΩ
    Electromagnetic compatibility Meet IEC 61000 standard (Level 4);
    Environment Operating temperature-25℃~+70℃;

    Storage temperature-40℃~+85℃;

    Relative humidity75% without condensation;

    Altitude2000m

    Protection Level Display panel IP54, with gasket;
    Standards IEC 60068-2-1

    IEC 60068-2-2

    IEC 60068-2-30

    Environmental Testing-Part 2-1:Tests Test A:Cold IDA

    Environmental Testing Part 2-2:Tests Test B:Dry heat

    Environmental Testing Part 2-30:Tests Test Db:Damp heatcyclic (12+12h)

    IEC 61000-4 Electromagnetic compatibility-Testing and measurement techniques
    IEC 61557-12 Electrical safety in low voltage distribution systems up to 1 000V a.c. and 1 500V d.c –Equipment for testing measuring or monitoring of protective measures Part12:Performances measuring and monitoring devices(PMD)
    IEC 62053-22 Electricity metering equipment (a.c.)-Particular requirements - Part22:Static meter for active energy(class 0.2S and 0.5S)
    IEC 62053-24 Electricity metering equipment (a.c.)-Particular requirements - Part24:Static meter for reactive energy at fundamental frequency (classes 0.5S 1S and 1)

    Note 1: Harmonic measurement 2~45 times in the range of frequency 45~65Hz, the error is ±1%, harmonic measurement 46~63 times at frequency 50Hz, the error is ±2%.