AMC16Z-FDK24/FDK48 DC Outlet Monitoring module

Short Description:

● Rated Voltage: 48VDC,240VDC,336VDC

● Rated Current: 5V (Hall sensor,external power supply ±12V)

 Communication: RS485 (MODBUS-RTU)

 Accuracy: Voltage/current level 0.5,power/electric energy level 1

 Auxiliary power supply: Get power supply from AMC16Z-ZD;DC 12-24V when used alone

 Installation: DIN35mm

● Standard&Certificate: CE; IEC; LVD;ROHS


Product Detail

parameter

General

AMC16Z series multi-loop acquisition module is independently designed to meet the needs of the increasingly high precision power distribution management requirements of the data center. It suitable for various all-round intelligent monitoring of terminal distribution equipment.

Function

● Monitor the full power parameters and switch state of 24(48) branches of A+B double-way AC outgoing line

● Measurement Voltage, Current, Frequency, Active Power, Reactive Power, Power Factor and etc

● 2nd~63rd&Total Harmonic 

Network Schemes

1

Product Selection

2

Wiring Diagram

1

Cabinet Diagram

2

Dimensions & Installation

3
4

AMC16Z-FAK24 Terminals

5

AMC16Z-FAK48 Terminals

6

Applications

7

Site Installation Photos

822

  • Previous:
  • Next:

  • Instrument model

    AMC16Z-FDK24

    AMC16Z-FDK48

    Measured parameter

    Voltage,current,power,electrical energy,switching state

     

    Bus voltage

    Rated

    48VDC,240VDC,336VDC

    Measured range

    ±20%

    Overload

    Instantaneous voltage 2 times per second

    Current out coming line circuit

    Rated

    5V (Hall sensor,external power supply ±12V)

    Range

    Overload

    Duration 1.2 times,instantaneous 10 times/second

    Measurement

    precision

    Outgoing line

    Voltage/current level 0.5,power/electric energy level 1

    Auxiliary power

    Get power supply from AMC16Z-ZD;DC 12-24V when used alone

    Environment

    Temperature

    Work: -15℃ ~ 55℃ Storage: -25℃ ~ 70℃

    Humidity

    Relative humidity ≤93%

    Altitude

    ≤2500m

    Communication

    RS485/Modbus-RTU

    Installation

    DIN35mm guide rail or floor mounted

    Protection level

    IP20

    Pollution levels

    2

    Security

    Insulation

    All terminals and the insulation resistance between the conductive pieces not below 100 m Ω

    Pressure

    A voltage current signal // B voltage current signal // Other ports meet AC2kV 1min between pairs,leakage current should be less than 2mA,

    no breakdown or flashing phenomenon.

     

    Electromagnetic compatibility

    Anti-static interference

    Class 4

    Radio frequency electromagnetic

    radiation

     

    Class 3

    Note: The secondary input voltage of AMC16Z-FDK module is 5V,and the default value of the primary side current is 50A.If the Hall sensor is different,the customer can set the ratio through the touch screen according to the actual use.