AMC16Z series multi-loop acquisition module is independently designed to meet the needs of the increasingly high precision power distribution management requirements of the data center. It suitable for various all-round intelligent monitoring of terminal distribution equipment.
● Monitor the full power parameters and switch state of 24(48) branches of A+B double-way AC outgoing line
● Measurement Voltage, Current, Frequency, Active Power, Reactive Power, Power Factor and etc
● 2nd~63rd&Total Harmonic
Instrument model |
AMC16Z-FAK24 |
AMC16Z-FAK48 |
||
Measurement parameters |
Voltage, current, frequency, active power, reactive power, power factor, active power, reactive power, switching state |
|||
|
2-31 times harmonics |
|||
Bus Voltage |
Rated |
220VAC |
||
|
Measurement |
±20% |
||
|
Overload |
Instantaneous voltage 2 times/second |
||
Current outgoing line loop |
Rated |
50mA |
||
|
Range |
0.125~60mA |
||
|
Overload |
Duration 1.2 times, instantaneous 10 times/second |
||
Input frequency |
45~60Hz |
|||
Measurement accuracy |
Outgoing line |
Voltage/current/active power/active energy level 0.5, reactive power/reactive energy level 1 |
||
Auxiliary power supply |
Power supply by AMC16Z-ZA;DC 12-24V when used alone |
|||
Environment |
Temperature |
Working:-15℃~55℃ Storage:-25℃~70℃ |
||
|
Humidity |
Relative humidity |
||
|
Altitude |
≤2500m |
||
Communication |
RS485/Modbus-RTU |
|||
Installation method |
DIN35mm Guide rail or bottom plate mounting |
|||
IP grade |
IP20 |
|||
Class of pollution |
2 |
|||
Safety |
Insulation |
All terminals and the insulation resistance between the conductive pieces not below 100 m Ω |
||
|
Withstand voltage |
A-channel voltage and current signal // B-channel voltage and current signal // other ports meet AC2kV 1min between pairs, leakage current should be less than 2mA, no breakdown or flash over phenomenon. |
||
Electromagnetic compatibility |
Anti static interference |
Level 4 |
||
|
Resistance to radiation of Radio frequency electromagnetic |
Level 3 |
Note: The rated of the secondary side input current of AMC16Z-FAK module is 50mA. The default value of the primary side is 50A. If the CT is different, the customer can set the ratio through touch screen or upper computer according to the actual usage.