AIM-T500L series industrial insulation monitoring and fault is specially developed by Acrel for IT distribution system in industrial occasions such as mine, glass factory, electric furnace and test equipment, ship, metallurgical plant, chemical plant, explosion hazard site, computer center and emergency power supply. The system has rich functions, including insulation resistance monitoring, insulation fault warning, insulation fault alarm, event recording, parameter setting, communication networking, etc. When the system has grounding fault, it can give a timely alarm and accurately locate the specific circuit of the fault to remind staff to check the fault in time.
Parameter
Item |
Parameter |
|
Accessory power supply |
AC 85~265V; DC100~300V; 50/60Hz |
|
Power dissipation |
< 8W |
|
System voltage |
AC 0~690V; DC 0~800V; 40~460Hz |
|
System application |
IT system (online), Other system (offline) |
|
Insulation monitoring |
Measuring range |
1k~10MΩ |
Alarm range |
10k~10MΩ |
|
Resistance accuracy |
1~10k,1k; 10k~10M, ±10% |
|
system leakage capacitance |
<500μF |
|
Response time (Ce=1μF) |
<5s |
|
Internal parameters |
Measuring voltage |
<50V |
Measuring current |
<270μA |
|
Internal DC impedance |
≥180kΩ |
|
Relay output |
Error, Alarm, Warning |
|
SOE |
20 records (fault type, fault value, fault time) |
|
Alarm type |
LCD, LED indicator |
|
Communication |
RS485, Modbus-RTU; CAN, custom |
|
Impulse voltage / Pollution Level |
8kV/Ⅲ |
|
EMC/ Radiation |
IEC61326-2-4 |
|
Environment |
Working temperature |
-10 ~+65℃ |
Storage temperature |
-20~+70℃ |
|
Relative humidity |
<95%, without condensation |
|
Altitude |
≤2500m |