AIM-T500L Industrial Insulation Monitor

Short Description:

● Can monitor AC,DC or AC/DC under 690V mixed ungrounded system

● DC ungrounded system under 800V to ground resistance and capacitance value

● With fault warning and alarm function

● Fault location function

● 1 channel RS485

● 1 CAN communication

 2 replay outputs

● Self-check function

● LCD display

● SOE event record


Product Detail

Parameter

General

AIM-T500L series industrial insulation monitoring and fault  is specially developed by Acrel for IT distribution system in industrial occasions such as mine, glass factory, electric furnace and test equipment, ship, metallurgical plant, chemical plant, explosion hazard site, computer center and emergency power supply. The system has rich functions, including insulation resistance monitoring, insulation fault warning, insulation fault alarm, event recording, parameter setting, communication networking, etc. When the system has grounding fault, it can give a timely alarm and accurately locate the specific circuit of the fault to remind staff to check the fault in time.  

Features

1

Dimension

2

Typical connection

4

Site installation pictures

5

  • Previous:
  • Next:

  •  Parameter

    Item

    Parameter

    Accessory power supply

    AC 85~265V; DC100~300V; 50/60Hz

    Power dissipation

    < 8W

    System voltage

    AC 0~690V; DC 0~800V; 40~460Hz

    System application

    IT system (online), Other system (offline)

    Insulation monitoring

    Measuring range

    1k~10MΩ

    Alarm range

    10k~10MΩ

    Resistance accuracy

    1~10k,1k; 10k~10M, ±10%

    system leakage capacitance

    <500μF

    Response time (Ce=1μF)

    <5s

    Internal parameters

    Measuring voltage

    <50V

    Measuring current

    <270μA

    Internal DC impedance

    ≥180kΩ

    Relay output

    Error, Alarm, Warning

    SOE

    20 records (fault type, fault value, fault time)

    Alarm type

    LCD, LED indicator

    Communication

    RS485, Modbus-RTU; CAN, custom

    Impulse voltage / Pollution Level

    8kV/Ⅲ

    EMC/ Radiation

    IEC61326-2-4

    Environment

    Working temperature

    -10 ~+65℃

    Storage temperature

    -20~+70℃

    Relative humidity

    <95%, without condensation

    Altitude

    ≤2500m