AIM-T500 Industrial Insulation Monitor

Short Description:

● Can monitor AC,DC or AC/DC under 690V mixed ungrounded system

● With fault warning and alarm function

● Connection monitoring of PE and IT systems.

● 1 channel RS485

 2 replay outputs

● Self-check function

● LCD display

● SOE event record


Product Detail

Parameter

General

AIM-T500 insulation monitoring device is designed and developed by Acrel gathering the design experience of electric power meter industry for many years to monitor the insulation condition of low voltage IT distribution system (ungrounded system). The product adopts advanced micro controller technology, with high degree of integration, compact size and easy installation, and it integrates intelligence, digitalization and networking. The device, with many functions such as insulation fault warning, fault alarm, event recording and so on, can be used in the mines, glass factories, electric furnaces and test facilities, metallurgical plants, chemical plants, and exploded dangerous places, computer center, emergency power supply and other places to monitor the insulation status of IT system in real time. When insulation fault occurs, it will alarm and remind the staff to check the fault.

Features

1

Dimension

2

Wiring

3

Typical connection

4

Site installation pictures

5

  • Previous:
  • Next:

  • Technical parameters

    Item

    Parameter

    Accessory power supply

    AC 85~265V; DC100~300V; 50/60Hz

    Power dissipation

    < 8W

    System voltage

    AC 0~690V; DC 0~800V; 40~460Hz

    System application

    IT system (online), Other system (offline)

    Insulation monitoring

    Measuring range

    1k~10MΩ

    Alarm range

    10k~10MΩ

    Resistance accuracy

    1~10k,1k; 10k~10M, ±10%

    system leakage capacitance

    <500μF

    Response time (Ce=1μF)

    <5s

    Internal parameters

    Measuring voltage

    <50V

    Measuring current

    <270μA

    Internal DC impedance

    ≥180kΩ

    Relay output

    Error, Alarm, Warning

    SOE

    20 records (fault type, fault value, fault time)

    Alarm type

    LCD, LED indicator

    Communication

    RS485, Modbus-RTU

    Impulse voltage / Pollution Level

    8kV/Ⅲ

    EMC/ Radiation

    IEC61326-2-4

    Environment

    Working temperature

    -10 ~+65℃

    Storage temperature

    -20~+70℃

    Relative humidity

    <95%, without condensation

    Altitude

    ≤2500m