AIM-M200 medical intelligent insulation monitor

Short Description:

● Accurate Insulation Resistance monitoring

● Load&Temperature monitoring for Insulation Transformer

● Prompt Alarm with Relay Output and LED Indicator once Insulation

Fault or IT System Devices Disconnection happened

● Smart HMI for convenient Parameter&Alarm Setting and Self-test

● Support Insulation Fault Location Function

● RS485&CAN bus Communication

● IEC 60364-7-710:2002;IEC62020-1:2020; EMC


Product Detail

Parameter

Download

Certification

Instructions

General

The AIM-M200 monitors the insulation resistance of medical IT system, At the same time, the load current and temperature of the IT system transformer is monitored. In combination with ASG100, AIL100 series insulation fault locators and the appropriate measuring current transformers, the AIM-M200 is designed to support insulation fault location.

Features

1

Dimension

2

Networking Scheme

4
5

Typical Application

6

  • Previous:
  • Next:

  • Technical Parameters of AIM-M200 Medical Intelligent Insulation Monitoring

    AUX Power

    Voltage

    DC 18~36V

    Temperature monitoring

    Thermal resistor

    Pt100

    Power consumption

    ≤3W

    Measuring range

    -50~+200℃

    Insulation monitoring

    Resistance measuring range

    15~999kΩ

    Alarm value range

    0~+200℃

    Response value

    50~999kΩ

    Alarm output

    Output mode

    Relays

    Relative uncertainty

    ±10%,±10K

    Contact rating

    AC 250V/3A

    DC 30V/3A

    Response time

    ≤3s

    Environment

    Operating temperature

    -10~+55℃

    Permissible system leakage capacitance Ce

    ≤5uF

    Transport temperature

    -25~+70℃

    Measuring voltage Um

    ≤12V

    Storage temperature

    -25~+70℃

    Measuring current Im

    ≤50uA

    Relative humidity

    5~95%,No condensation

    Impedance Zi

    ≥200kΩ

     

    Altitude

    ≤2500m

    Internal DC resistance Ri

    ≥240kΩ

    IP degree

    IP30

    Permissible extraneous DC voltage Ufg

    ≤DC280V

    Rated impulse voltage

    / pollution degree

    4KV/Ⅲ

    Load current monitoring

    Measuring Value

    2.1~50A

    EMC/EMR

    IEC 61326-2-4

    Alarm Value

    5~50A

    Communication protocol

    CAN, customize

    Measuring accuracy

    ±5%

    RS485,

    Modbus-RTU