AIM-D100-T series DC Insulation Monitor

Short Description:

● Auxilliary Power : DC 9~36V

● Maximum power comsumption: ≤6W

● Voltage range: AIM-D100-TH: DC 100~1000V;AIM-D100-TL: DC 10~100V

● Accuracy :0.5

● Overvoltage threshold: ≥110% Rated Voltage

● Undervoltage threshold: ≤90% Rated Voltage

● Insulation resistance range:1kΩ~10MΩ

● Warning and alarm range: 10kΩ~10MΩ 


Product Detail

General

With the development of industry, many electrical equipment and plant equipment are powered by DC systems, which have ungrounded positive and negative terminals. For ungrounded (IT) distribution system, insulation resistance should be monitored to ensure the safe operation of the power supply system.AIM-D100-T series DC insulation monitor can be applied in 10~1000V DC system for on-line monitoring of DC ungrounded system positive and negative pole to ground insulation resistance, and send out warning or alarm signal when insulation resistance is lower than the set value.
AIM-D100-TH(L)_R

 

 

 

The product is based on the principle of unbalanced bridge, which avoids the problem that balanced bridge can not detect the insulation resistance when there are ground faults at both positive and negative poles.

The product can be applied to DC systems such as DC panels of power plants and substations, electric vehicle charging devices, UPS power supply systems, photovoltaic DC systems, energy storage systems and other DC power grids

 

Dimension

1710311620469

Technical parameter

1710311247126
Technical Parameter
Technical Specifications
Auxiliary power
DC 9~36V
Maximum power consumption
≤6W
 
 
Voltage
monitor
Voltage range
AIM-D100-TH: DC 100~1000V;
AIM-D100-TL: DC 10~100V
Accuracy
0.5
Overvoltage threshold
≥110% Rated Voltage
Undervoltage threshold
≤90% Rated Voltage
 
 
Insulation
monitoring
Insulation resistance range
1kΩ~10MΩ
Warning and alarm range
10kΩ~10MΩ
Accuracy
1~10kΩ: ±1k; 10k~500k: ≤3%
System leakage capacitance
≤5μF
Monitoring method
Cycle trigger: 5~500s delay can be set;
Communication trigger: read on demand
Insulation monitoring speed
500ms/cycle; 1000ms/cycle
 
Internal DC impedance
<1MΩ
Alarm method
LCD, LED indicator, relay output
Alarm output
3 relay outputs, N/O or N/C can be set
Contact capacity
5A 250V AC;5A 30V DC
Fault Record
20 fault record
Communication
RS485 interface, Modbus-RTU protocol
Installation
DIN-rail installation
Protection level
IP30
 
 
 
Environment
Operating temperature
-40~+75℃
Storage temperature
-40~+125℃
Relative humidity
<95%, without condensation
Altitude
<2000m