Online&Remote Energy Monitoring
● Paired with Acrel IoT Energy Monitoring System
● PC Access via IoT EMS WEB
● Mobile Phone Access via IoT EMS APP
● 4G Wireless Communication (Global)
● WiFi Wiress Communication (2.4GHz)
● Support MQTT, MODBUS-TCP protocol
● Support standard RS485 interface (MODBUS-RTU)
1. Function Overview
Function | Description |
Measurement
(Standard)
|
Single-phase AC Active&Reactive Energy (both forward and backward), Active Power, Reactive Power, Current, Voltage, Frequency, Power Factor, Apparant Power, Frequency |
Measurement
(Optional)
|
Temperature Measurement:2-channel (Live line,Neutral line) Cable Temperature Monitoring; Thermistor:NTC; Range: -40~+99℃; Accuracy:±2℃ |
Communication
(Standard)
|
RS485 Port with Modbus-RTU protocol - 1 start bit,8 data bit,1 stop bit,no parity; Baud Rate 1200~38400 bps etc. Infrared Communication – Constant Baud Rate 1200 bps |
Communication
(Optional)
|
4G LTE – Normal Communicaiton Module Support: LTE-FDD: B1/B3/B5/B8; LTE-TDD:B34/B38/B39/B40/B41 4G LTE – Global Communication Module Support: LTE-FDD:B1/B3/B5/B7/B8/B20/B28; LTE-TDD:B38/B40/B41 |
WiFi – Support 2.4GHz or 5GHz |
|
Protocol (For wireless Communication): MQTT and MODBUS-TCP |
|
Display
(Standard)
|
LCD Display and LED Indicator |
HMI
(Standard)
|
Keypads Programming: Setting of CT/PT Ratio, Communication, Phase Wiring and etc |
Software
(Standard)
|
Adjustment Software: Setting of Data Upload Interval, WiFi configuration (Account&Password), Server Address, Port and etc |
Alarm Function
(Standard)
|
Undervoltage, Overvoltage, Undercurrent, Overcurrent, Underload, Overload, Communication Disconnection and etc |
I/O Function
(Optional)
|
1-channel DI (Digital Input) 1-channel DO (Digital Output) |
2. Main Parameters
Parameter | Description&Value | |
Voltage
Input
|
Rated Voltage | 220~264Vac L-N |
Reference Frequency | 45~65Hz | |
Power Consumption | <0.5VA (each Phase) | |
Current
Input
|
Rated Current | 20(100)A AC |
Starting Current | 1% Ib (Class 0.5); 4% Ib(Class 1) | |
Power Consumption | <1VA (each Phase) | |
Phase
Wiring
|
1P2W | 1-phase 2-wire |
Measurement
Performance
|
Standard | GB/T17215.322-2008,GB/T17215.321-2008 |
kWh Accuracy | Class 1 | |
Pulse
|
Width of Pulse | 80±20ms |
Pulse Constant | 1600imp/kWh; |
3. Environment
Condition | Description&Value |
Temperature
|
Operating Temperature: -25℃~+55℃; Storage Temperature: -40°C ~+70°C |
Humidity
|
≤95%RH,no condensation,without corrosive gas |
Altitude
|
≤ 2000m |