ADF400L Multi-circuits Prepaid Energy Meter

Short Description:

● Measurement: 1-phase&3-phase kWh (Class 0.5S), kVarh, Active Power, Reactive Power, Current, Voltage and etc

● Voltage: Three phase 3*220V/380V

● Current: 3×1(6)A(via CT),3×10(80) (Directly)

 Accuracy: Class 0.5S

● Power Supply:3*220/380V or 220V AC

● Standard&Certificate: CE

● Installation: 35mm Din Rail


Product Detail

parameter

Detail

1

Compact Modular Design

● Main Body (LCD&Keypads HMI)

● 1-phase Metering Module

● 3-phase Metering Module

● Expanded Communication Module

2
3

Multi Circuits Metering for 1-phase&3-phase

● 3 Types of Multi-circuits Combination

● Max 36 Circuits 1-phase Metering

● Max 12 Circuits 3-phase Metering

● Mixed (1-phase&3-phase Circuits Metering)

Remote Switch Control

● Control&Read Status of Switches

● 2 DO&2 DI (Main Body)

● Dry Contact DI (Main Body)

● 4 DO&4 DI (CT operated Sub Module)

● 220V AC Wet Contact DI (CT operated Sub Module)

4

Module Overview

Main Body

● Max 36 Circuits 1-phase or 12 Circuits 3-phase

● Max 12 Modules (1-phase) or 6 Modules (3-phase)

● RS485 (MODBUS-RTU); Ethernet

● LCD&Keypads HMI

5
6

Sub Module (Connection via CTs)

● Monitor Max 2 Circuits 3-phsae

● 3x1(6)A AC (CT Operated Connection)

● 4DO&4DI (220V AC Wet Contact DI)

● LED Indicator

Sub Module (Direct Connection)

● Monitor Max 3 Circuits 1-phase or 1 Circuits 3-phase

● Max 80A AC Direct Load Current

● LED Indicator

7
8

Expanded Communication Module

Upstream: 4G/WiFi/LoRa/LoRaWAN/NB-IoT

Downstream: RS485 (MODBUS-RTU)

RJ45 Interface (connected with Main Body)

Power Supply: 24V/12V DC or 220V AC/DC

Dimensions(Unit:mm)

9
10

Wiring

11

Typical Connection

12

Live Application Pictures

13

  • Previous:
  • Next:

  • Prepaid

    Features

    Function Description

     

    Energy metering

     

    Electricity measurement

    Total active energy, forward and reverse active energy, multi-rate active energy

    measurement

    U、I

    P、Q、S、PF、F

    LCD display

    8-digit segment LCD display, backlight display

    Button

    programming

    Key programmable communication, number of loops, single three-phase mode,

    external control mode and other parameters

    Pulse output

    Active pulse output

     Multiple rate

    Support 4 time zones, 2 time slots, 14 daily time slots, 4 rates

    Date, time, day of the week

     Main module communication

    Infrared communication

    Up to 3 channels of communication: RS485 interface,

     

    Also support Modbus

     

    Prepaid agreement (remote, radio frequency card)

    Cost control (including forward active power and reverse active power)

    Time control

    Negative control (malignant load identification)

    Strong control

    Recharge record

    20 Article

    Metering type

    Features

    Function Description

    Display method

    LCD(Field)

     Energy metering

    Active energy metering(Forward and reverse),

    Reactive power measurement(Forward and reverse),

    Electricity

    measurement

    Voltage, current (zero sequence current), power factor, frequency, active power, reactive power,

    apparent power

    Harmonic function

    Total harmonic content, sub-harmonic content (2~31 times)

    Three-phaseunbalance  

    Voltage and current unbalance

     

    DI/DO

    Main module 2DI2DO

    Transformer access to the slave module 2DI4DO (direct access to the slave module without)

    LED Instructions

    Pulse light indication

     Communication

    Infrared communication

    RS485 interface (main module) supports MODBUS

    Historical power

    Historical Electricity in Last December

    Technical parameter

    technical parameter model

    ADF400L-□H□S□D(Y)- □

     Auxiliary power  Voltage

    Three-phase 3*220V/380V power supply (for single-phase power supply,

    short-circuit terminals 1, 2, and 3 on the instrument)

    Powerconsumption  

    ≤10W

     Voltage input Rated voltage

    3×220/380V、3×57.7/100V、

    Referencefrequency  

    50Hz

     Current input Input Current

    3×1(6)A(Instrument transformer access), 3*10 (80) (direct access)

    Starting current

    1‰Ib

     Measuring performance measurementaccuracy  

    0.5s level

    Clock accuracy

    ≤0.5s/d

      Pulse Pulse output

    Each three-phase metering module has 1 active energy pulse

    Pulse Width

    80ms±20ms

    Pulse constant

    3×1(6)A specification 6400 imp/kWh

     

       

    3×10(80)A specification 400 imp/kWh

     Switch Main module

    Main module 2DI+2DO,Among them, DI is dry contact input

     Slave module

    Transformer access slave module 4DI+4DO,Among them, DI is 220V wet contact

    input

     Communicatio n Infrared interface

    Infrared communication

    RS485 interface

    MODBUS-RTU

    Ethernet interface

    Modbus-TCP、TCP/IP

      Surroundings temperature

    Operating temperature:-20℃~+60℃,

    storage temperature:-30℃~+70℃

    humidity

    ≤95%RH,No condensation, no corrosive gas place

    altitude

    ≤2000m