Technical parameter
Technical parameters |
Indicators |
|||
Input |
Net work |
3-phase 3-wire,3-phase 4 wire |
||
Frequency |
45~65Hz |
|||
Voltage |
Rating:AC 57.7V/100V(100V)、220V/380V(400V) |
|||
Overload:1.2-fold rating(continuous);2-fold rating/1second |
||||
Consumption:<0.2VA |
||||
Current |
Rating: 80A,120A,200A .etc(See specific product specifications,special parameters can be customized) |
|||
Overload:1.2-fold rating(continuous);10-fold rating/1 second |
||||
Consumption:< 0.2VA |
||||
Output |
Electric energy |
Output mode:Open-collector photocoupler pulse,two way output |
||
Three-phase |
Pulse constant:4000、8000imp/kWh |
|||
Communication |
RS485 interface,Modbus-RTU Protocol |
|||
Display mode |
LCD |
|||
Function |
Switching |
Input |
Four way dry contact input |
|
Output |
Output mode: two way relay nO contact output |
|||
Contact capacity:AC 250V/3A、DC 30V/3A |
||||
Measuring accuracy |
Frequency0.05Hz、reactive electric energy1class、other 0.5class |
|||
Power supply |
AC85~265V or DC100~350V;DC24V(±10%);DC48V(±10%) Consumption≤10VA |
|||
Safety |
Power-frequency withstand voltage |
Power frequency withstand voltage between Auxiliary power and switch volume output and current input and voltage input and communication and pulse output and switch volume input terminal is AC2kV 1min;Power frequency withstand voltage between auxiliary power and switch volume output and current input voltage input terminal is AC 2kV/1min;Power frequency withstand voltage between communication and pulse output and switch volume input terminal is AC 1kV/1min; |
||
Insulation resistance |
Input,Output terminal to housing>100MΩ |
|||
Environment |
Working temperature:-10℃~+55℃;Storage temperature:-20℃~+70℃ Relative humidity:5%~95% No condensation;Altitude:≤2500m |